Butt fusion heating and cooling times DVS 2207-11 - Aquatherm

Butt fusion heating and cooling times DVS 2207-11

 202008A – AQTTB 

 Date Issued: 12-Aug-2020 

 The standard referenced for butt fusion of polypropylene pipe, DVS 2207-11, was updated in 2017 to provide for reduced heating and cooling times. During the revision process, these changes were not evaluated for multi-layer, faser-composite (MF) pipes. Aquatherm has now completed the testing and evaluation of these changes and has adopted them for use across all sizes/SDRs of Aquatherm MF piping. 

The following is a brief description of the butt fusion parameters and identification of any changes between the previous version (2008) and current standard (2017). Any changes are noted in red. 

 Table 1 – Changes other than heat/cool times 

 Item  Description of change 
Permissible gap between pipe ends after facing/planing  No change 
Permissible misalignment of pipe ends (max 10% of wall thickness)  No change 
Heater temperature, 210±10°C (410±18°F)  No change 
Equalizing pressure (previously alignment pressure in 2008) – Bead-up/adjustment in Installer Manual  No change to actual interfacial pressure (14.5 psi), just name change 
Preheating pressure (previously heating-up pressure in 2008) – Heating pressure in Installer Manual  No change to actual interfacial pressure (14.5 psi), just name change 
Joining pressure – Machine pressure in Installer Manual  No change 
Bead height  No change for existing sizes/wall thicknesses, added requirement for wall thickness above 1.97 in. (50-70mm) 

 

Table 2 – Reduction in Heating Times from 2008 Edition 

Wall, mm Heat time, sec.
DVS 2207-11
Reduction
2008 2017
4.5 135 53 -61%
7 175 81 -54%
12 245 135 -45%
19 330 206 -38%
26 400 271 -32%
37 485 362 -25%
50 560 450 -20%
70 NA 546 New

 

Table 3 – Reduction in Fusion/Cooling Times from 2008 Edition 

Wall, mm  DVS 2207-11 Reduction at 60-80°F 
2008 2017
Ambient temperature at time of fusion
Standard ≤60°F (≤15°C) 60-80°F (15-25°C) >80°F (>25°C)
4.5  6  4  5  6.5  -17% 
7  12  6  7.5  9.5  -38% 
12  20  9.5  12  15.5  -40% 
19  30  14  18  24  -40% 
26  40  19  24  32  -40% 
37  55  27  34  45  -38% 
50  70  36  46  61  -34% 
70  NA  50  64  85  New 

 

Reducing cooling time under pressure, removal of equipment 

Butt fusion needs to cool under pressure to ensure proper connections. Cooling times under pressure for butt fusion connections can be reduced if the joint is supported properly and not subjected to any loads for the remainder of the cooling time. 

For example, at 70°F the cooling time for 6 in., SDR 11 pipe can be reduced from 14 minutes to 9 minutes if the joint is not subjected to any stress for the remaining 5 minutes. 

Table 4 – Reduced cooling times under pressure with no load on joint and proper support 

Wall, mm Cooling time, minutes
DVS 2207-11 (2017)
≤60°F  60-80°F  >80°F  Reduced time* 
4.5  4  5  6.5  3.5 
7  6  7.5  9.5  5 
12  9.5  12  15.5  8 
19  14  18  24  12 
26  19  24  32  16 
37  27  34  45  23 
50  36  46  61  31 
70  50  64  85  43 

*No load on joint, properly supported for the full duration of the standard cooling time

 

arrow_upward