AQUATHERM RED PIPE AND NFPA 24-2013
201606A-AQTTB
Date Issued: 9 June 2016
With regard to the use of Aquatherm red pipe at a location within the scope of NFPA 24, “Installation of Private Fire Service Mains and Their Appurtenances”, the standard allows for equivalency when a product is not explicitly noted in the table of piping materials (Sec. 1.4). This section allows the use of systems with equivalent or superior quality, strength, fire resistance, effectiveness, durability and safety when compared to products prescribed in the standard.
Chapter 10 of NFPA 24 – 20191 covers underground piping. Section 10.1.1 specifies that piping shall be listed for fire protection service or shall comply with one of the standards in Table 10.1.1. The Aquatherm red pipe is listed by Factory Mutual for fire suppression systems. FM does not yet have a listing program developed for underground fire protection systems, but there is a standard for polyethylene (PE) pipe for underground service. Table 1 provides a comparison of requirements.
Table 1 – Comparison of Minimum Requirements for Listing1
Underground PE vs. Fire Suppression PP-R
Standard | Polyethylene Pipe | Polypropylene (PP-R) Pipe |
Requirement | FM,16132 Underground PE | FM,16352 Fire Suppression PP-R |
Minimum pressure rating | 150 psi at 73°F | 175 psi at 120°F |
Potable water | PE resin NSF 61 | PP resin NSF 61 |
Hydrostatic strength | 4x WP for 5 min. | 5.1-8.5 x WP depending on size |
Pressure cycling | None | Piping and joints withstand 100,000 pressure cycles |
Flattening/crush resistance | Max. deflection 5% to 8 ft. burial depth | 200 lb. load, pipe/fitting, max. deflection 0.4% under H20 highway loading at 8 ft. depth |
High Ambient Temperature Exposure | None | 45 days, 200°F, <5% reduction in waterway |
Ring-tensile strength | 2500 psi min. | Not required, but can be calculated from burst test data, 2800-4665 psi |
120°F sustained pressure | None | 45 days |
Temperature cycling test | None | -40°F to 120°F, 10 days, then pressure test |
Vibration | None | 18-37 Hz, and resonant frequencies |
Head loss (Resistance to flow) | None | Verify mfr. claim for Hazen-Williams C-factor |
Damage resistance | None | 10% wall thickness damage, must still pass hydrostatic test |
Bending moment resistance | None | Quick-burst test while at max bending per mfr. literature |
Thermal expansion/contraction | None | Must withstand hydrostatic test while under max tensile stress from ΔT = 100°F |
1-There are additional tests not shown in the table related to manufacturing and QC, such as elongation, bend-back,
and impact. These were not included because there is not a direct means of comparison between the different
materials (e.g. can’t directly compare the PE bend-back test to the PP-R impact test).
As seen in Table 1, the Aquatherm red pipe would be considered to meet or exceed the
requirements of one of the materials prescribed in the standard (PE). Additionally, with regard to fire exposure, the Aquatherm red pipe has met the UL requirements for fire exposure testing.
The NFPA 24 standard also has a provision for allowing “Special Listed Fittings” in Section 10.2.3. This section specifically references fittings which have been investigated for suitability in automatic sprinkler systems as being permitted under NFPA 24. The Aquatherm red pipe fittings and fusion-weld joining method are included in the FM listing for this application.
Revisions
- 8 Dec 2021 – Code updates
- 21 Dec 2023 – Code numbers updated